1. Study Criteria

2. Motor Inputs

Select motors and complete all highlighted study inputs. Values loaded from the One-Line remain editable for this study run.

Load motors from the active One-Line Diagram to begin.

3. Results

No study has been run.

Supported Starter Types

Choose a starting method for each motor above. The study applies these screening models:

Starting Method Inrush Model Key Parameters
dol (default) Full locked-rotor current (6× FLC typical) inrushMultiple
vfd Current limited to vfd_current_limit_pu × FLC (default 1.1×) vfd_current_limit_pu, ramp_time_s
soft_starter Voltage ramps from initial_voltage_pu to 1.0; starting current ∝ V and torque ∝ V² initial_voltage_pu (0.3), ramp_time_s (10)
wye_delta Inrush = Ilr ÷ 3 during wye phase; full inrush after switch wye_delta_switch_time_s (5)
autotransformer Inrush × tap²; typical tap 0.65 autotransformer_tap (0.65)