Design Rule Checker
Current project validation
Design Rule Results
Review active errors and warnings first. Calculation options and the check methodology remain available below.
Run Options Tray-fill limit and optional check exclusions
Method & Checks Performed
The Design Rule Checker (DRC) validates your routing project against NEC and IEEE requirements after routing has been completed in the Optimal Route tool. Run the DRC after every routing session to catch code violations early.
- DRC-01 — Tray Fill (NEC 392.22(A))
- Evaluates each tray against the NEC 392.22(A) allowance. Trays with barriers (more than one slot) are checked compartment by compartment; a cable is placed by its slot index, a cable group that matches the tray's slot groups, or its zone (compartment number). When cable data is unavailable, a clearly labeled aggregate capacity screen (default 40 %) is used instead.
- DRC-02 — Voltage Segregation (NEC 392.6(H))
- Detects tray segments containing cables from different cable groups (e.g., HV and LV cables sharing the same tray without a physical barrier).
- DRC-03 — Ampacity Adjustment (NEC 392.80(A)(1)(a))
- Applies Table 310.15(C)(1) adjustment only to multiconductor cables with more than three current-carrying conductors, using the count in each cable (not the tray total), and flags cables whose design current (design current, load amps, or the schedule's Est Load) exceeds the adjusted ampacity.
- DRC-04 — Grounding Conductor (NEC 250.122)
- Warns when a power cable record does not include a grounding (EGC) conductor size.
- DRC-05 — Unrouted Cables
- Lists cables present in the Cable Schedule that have no assigned tray or field route after routing.
- DRC-10 - Conduit Fill (NEC Chapter 9)
- Screens assigned conduit/raceway cables against selected Chapter 9 Table 1 fill limits when conduit type, trade size, and cable OD or area data are available.