N-1 Contingency Analysis
Automatically remove each branch in the one-line model and check for voltage violations and branch overloads.
Method & Assumptions
For each branch (cable, transformer, or tie) in the one-line diagram, the branch is removed and a Newton–Raphson load flow is re-solved. Violations are flagged when:
- Bus voltage departs from the configured per-unit bounds (default 0.95–1.05 pu)
- A branch loading exceeds the configurable threshold (default 100% of rating)
- The modified network fails to converge (indicates an island or severe overload)
When "Check rotor angle stability" is enabled, a classical one-machine infinite-bus (OMIB) swing equation is solved for each generator-connected bus. Pre-fault and post-fault maximum power transfer are estimated from the 30° operating-angle assumption and the post-contingency voltage ratio. If the rotor angle exceeds 180° before re-synchronisation, the contingency is flagged as transient instability.
Results are stored in the project's Studies object and can be referenced by other tools.
Prerequisites: Define buses and branches in the One-Line Diagram editor and run a base-case Load Flow study first.
Study Parameters
Results
| Branch Removed | Type | Converged | Violations | Status | Transient Stability |
|---|---|---|---|---|---|
| Run the study to see results. | |||||