Method — NEC 210.20 / 215.3 / 240.4 / 310.15 / 392.80

For continuous loads (≥3 hours): conductor ampacity and OCPD rating must be at least 125% of the load current (NEC 210.20(A), 215.3).

Conductor size is selected from NEC Table 310.16 baseline ampacity values (formerly Table 310.15(B)(16)). Ambient temperature, bundling, and cable tray correction factors per NEC 310.15(B)(1)(a), 310.15(C)(1), and 392.80(A) are applied based on the Installation Conditions you enter below.

NEC 110.14(C) terminal-temperature limits are applied separately from the insulation ampacity table. Leave the terminal rating blank to infer 60 C through 100 A equipment and 75 C above 100 A.

OCPD rating is the next standard rating from NEC 240.6(A) at or above required load ampacity (NEC 240.4(B)). For small conductors, NEC 240.4(D) limits maximum OCPD to #14 Cu = 15A, #12 Cu = 20A, #10 Cu = 30A, #12 Al = 15A, and #10 Al = 25A.

Input Mode
Load Parameters

NEC 110.14(C) screen: blank infers 60 C through 100 A equipment and 75 C above 100 A.

Installation Conditions

NEC Table 310.15(B)(1)(a) — reference 30°C; derating applies above 30°C

NEC 310.15(C)(1) — derating applies when > 3 conductors

NEC 392.80(A) — 0.65× factor applies when single-conductor cables touch in tray